We use cookies. For more information go to privacy policity
RU
+7 (342) 279-75-55
+7 (908) 270-75-55

Heating cables

Self-regulated cable BSX

bsx-thermon.pngFreeze Protection or Process Temperature Maintenance BSX self-regulating heating cables are designed to provide freeze protection or process temperature maintenance to metallic and nonmetallic piping, tanks and equipment. The heat output of BSX cable varies in response to the surrounding conditions along the entire length of a circuit.

Whenever the heat loss of the insulated pipe, tank or equipment increases (as ambient temperature drops), the heat output of the cable increases. Conversely, when the heat loss decreases (as the ambient temperature rises or product flows), the cable reacts by reducing its heat output.

Cable BSX

Thermon offers system accessories designed specifically for rapid, trouble-free installation of Thermon heatingcables.

All cables require a connection kit to comply with approval requirements. Information on accessories to completea heater circuit installation can be found in the “Heating Cable Systems Accessories” product specification sheet (Form TEP0010).

Construction Thermon BSX

TubeTrace-SE-ME-bsx-construction.png1. Nickel-plated copper bus wires (16 AWG).

2. Radiation cross-linked semiconductive heating matrix.

3. Radiation cross-linked dielectric insulation.

4. Tinned copper braid.

5. Polyolefin overjacket provides additional protection for cable and braid where exposure to aqueous inorganic chemicals is expected.

Features

  1. Freeze protection
  2. Low process temperature maintenance
  3. No steam clean
  4. Certified for use in ordinary (nonclassified) areas and in potentially explosive atmospheres

Options

6 FOJ Fluoropolymer overjacket over tinned copper braid provides additional protection to cable and braid where exposure to organic chemicals or corrosives is expected.

Ratings Thermon BSX

  • Available watt densities: 3, 5, 8, 10 w/ft @ 500F
    (10, 16, 26, 33 w/m @ 10°C)
  • Supply voltages: 110-120 or 208-277 Vac
  • Max. maintenance temperature:150°F (65°C)
  • Max. continuous exposure temperature (power-off): 185°F (85°C)
  • Minimum installation temperature: OJ: -60°F (-51°C)
  • Minimum bend radius:
    5°F (-15°C): 0.38” (10mm)
    -76°F (-60°C): 1.25” (32 mm)
  • T-rating:
    3, 5, 8 w/ft (10, 16, 26 W/m) ...............T6 185°F (85°C)
    10 w/ft (33 W/m) ...............................T5 212°F (100°C)

Power output curves

The power outputs shown apply to cable installed on insulated metallic pipe (using the procedures outlined in IEEE 515) at the service voltages stated below. For use on other service voltages, contact Thermon.

Catalog number 120 Vac Nominal Catalog number 240 Vac Nominal Power Output at 50°F (10°C) w/ft (m)
BSX 3-1 BSX 3-2 3 (10)
BSX 5-1 BSX 5-2 5 (16)
BSX 8-1 BSX 8-2 8 (26)
BSX 10-1 BSX 10-2 10 (33)

Circut breaker size BSX

Maximum circuit lengths for various circuit breakeramperages are shown below. Breaker sizing should be based on the National Electrical Code, Canadian ElectricalCode or any other applicable code. The National Electrical Code and Canadian Electrical Code require ground-fault protection of equipment for each branch circuit supplying electric heating equipment. Check local codes for ground-fault protection requirements

120 vac service voltage Max. circuit length vs. breaker size ft (m)
Catalog number Start-up temperature 0F (0C) 20А 30А 40А
BSX 3-1 50 (10) 360 (110) 360 (110) 360 (110)
0 (-18) 325 (99) 360 (110) 360 (110)
-20 (-29) 285 (87) 360 (110) 360 (110)
-40 (-40) 260 (79) 360 (110) 360 (110)
BSX 5-1 50 (10) 240 (73) 300 (91) 300 (91)
0 (-18) 205 (62) 300 (91) 300 (91)
-20 (-29) 185 (56) 275 (84) 295 (90)
-40 (-40) 165 (50) 250 (76) 265 (81)
BSX 8-1 50 (10) 190 (58) 240 (73) 240 (73)
0 (-18) 150 (46) 225 (69) 240 (73)
-20 (-29) 135 (41) 200 (61) 240 (73)
-40 (-40) 120 (37) 180 (55) 215 (66)
BSX 10-1 50 (10) 160 (4) 200 (61) 200 (61)
0 (-18) 110 (34) 170 (52) 200 (61)
-20 (-29) 100 (30) 150 (46) 200 (61)
-40 (-40) 90 (27) 135 (41) 180 (55)
240 vac service voltage Max. circuit length vs. breaker size ft (m)
Catalog Number Start-up temperature 0F (0C) 20А 30А 40А
BSX 3-2 50 (10) 725 (221) 725 (221) 725 (221)
0 (-18) 650 (198) 725 (221) 725 (221)
-20 (-29) 575 (175) 725 (221) 725 (221)
-40 (-40) 515 (157) 725 (221) 725 (221)
BSX 5-2 50 (10) 480 (146) 600 (183) 600 (183)
0 (-18) 395 (120) 590 (180) 600 (183)
-20 (-29) 350 (107) 525 (160) 590 (180)
-40 (-40) 315 (96) 475 (145) 530 (162)
BSX 8-2 50 (10) 385 (117) 480 (146) 480 (146)
0 (-18) 285 (87) 425 (130) 480 (146)
-20 (-29) 255 (78) 380 (122) 480 (146)
-40 (-40) 230 (70) 345 (116) 430 (131)
BSX 10-2 50 (10) 280 (85) 400 (122) 400 (122)
0 (-18) 225 (69) 340 (104) 400 (122)
-20 (-29) 200 (61) 300 (91) 400 (122)
-40 (-40) 180 (55) 275 (84) 365 (111)
Enter correct name
Please enter a valid email address
Enter message text
* — required fields
Confirm that you are not a robot
Enter correct name
Please enter a valid email address
* — required fields