Heating cables

Self-Regulating Heating Cable KSX

Application

thermon-ksx.jpgHigh performance KSX self-regulating heating cables are designed specifically for high heat loss freeze protection applications or process temperature maintenance where steam cleaning is not required.

The heat output of KSX cable varies in response to the surrounding temperature by reducing its thermal output with increasing temperature.

KSX cables are certified for use in ordinary (nonclassified) areas and in potentially explosive atmospheres in accordance with the ATEX Directive and the IEC Ex Scheme.

Features Cable KSX

  1. Freeze protection.
  2. Low process temperature maintenance.
  3. Withstands continuous flammability testing according to IEC 60332-1: 1993.
  4. Can be installed at temperatutes to - 60 oC.

Rating Thermon KSX

Available watt densities 15, 32, 48, 64 W/m @ 10°C
Nominal supply voltages 230 Vac
Max. maintenance or exposure temperature Continuous power-on 121°C
Minimum installation temperature - 60°C
Minimum bend radius - 15°C 10 mm
- 60°C 32 mm
T-rating based on stabilized design T3 to T6

Construction Thermon KSX

Конструкция Thermon KSX1. Nickel-plated copper bus wires (1.3 mm2)

2. Semiconductive heating matrix and fluoropolymer dielectric insulation.

3. Tinned copper braid.

4. Fluoropolymer overjacket provides additional protection to cable and braid where exposure to chemicals or corrosives is expected.

Power output curves

The power outputs shown apply to overjacketed cable installed on insulated metallic pipe at the service voltage stated below.

Product Type, 230 Vac Nominal Power Output at 10°, CW/m
KSX 5-2 15
KSX 10-2 32
KSX 15-2 48
KSX 20-2 64
KSX at 230 Vac

Circuit breaker sizing and type

Maximum circuit lengths for various circuit breaker amperages are shown below. Circuit breaker sizing and earth-fault protection should be based on applicable local codes. For information on design and performance on other voltages, contact Thermon. Earth-fault protection of equipment should be provided for each branch circuit supplying electric heating equipment.

Type B Circuit Breakers

230 Vac Service Voltage Max. Circuit Length vs. Breaker Size, meters
Product Type Start-Up Temperature 16A 25A 32A
KSX 5-2 10 114 167 167
0 114 167 167
- 20 112 167 167
- 40 94 160 167
KSX 10-2 10 76 117 117
0 76 117 117
- 20 73 117 117
- 40 64 106 117
KSX 15-2 10 47 77 94
0 45 74 94
- 20 41 67 89
- 40 37 60 79
KSX 20-2 10 34 55 73
0 33 52 69
- 20 30 48 62
- 40 27 43 57

Type C Circuit Breakers

230 Vac Service Voltage Max. Circuit Length vs. Breaker Size, meters
Product Type Start-Up Temperature 16A 25A 32A
KSX 5-2 10 114 167 167
0 114 167 167
- 20 113 167 167
- 40 95 163 167
KSX 10-2 10 76 117 117
0 76 117 117
- 20 75 117 117
- 40 64 106 117
KSX 15-2 10 47 77 94
0 47 77 94
- 20 47 76 94
- 40 37 60 91
KSX 20-2 10 39 64 81
0 39 64 81
- 20 36 59 78
- 40 33 53 70