RTF FlexiPanel
Reservoir, tank and vessel heating panel Thermon RTF FlexiPanel
Application RTF FlexiPanel
The RTF FlexiPanel is a self-contained, high performance flexible heating panel designed specifically for use on fiberglass and plastic tanks or vessels and for metallic tanks and vessels containing high viscosity or temperature-sensitive fluids. Designed to provide heat outputs at 0.7 watts per square inch (1,085 watts per square meter) or less, the RTF FlexiPanel distributes heat evenly over the entire panel surface to maintain stable temperatures.1The low profile flexible design of the panel permits rapid, trouble free installation using the mounting kit available from Thermon.
To ensure multiple flow paths for electrical current to pass, the RTF FlexiPanel utilizes a parallel circuit design based on a stamped high temperature alloy heating element. This design eliminates the burnout potential common with series wire-based designs. The rugged construction of the RTF FlexiPanel includes a tough metal jacket that provides mechanical protection during handling and installation. The panel’s heating element is further protected from vibration and moisture by sandwiching it in a heat-laminated layer of silicone rubber that provides cushion and a watertight seal. RTF FlexiPanels are approved for use in ordinary (nonclassified) and hazardous (classified) areas.
Features of Thermon RTF FlexiPanel
- Reservoir, tank or vessel heating
- Specifically designed for fiberglass and plastic tank or vessels
- Even heat distribution
- Cirtified for use in ordinary (nonclassified) areas and in potentially explosive atmospheres
Construction of Thermon RTF FlexiPanel
1. High temperature lead wires (16 AWG)2. Protective metal jacket
3. Parallel circuit high temperature alloy heating element
4. Heat-laminated, high temperature silicone rubber insulation
Ratings of Thermon RTF FlexiPanel
- Nominal output: 300 and 500 watts
- Supply voltage: 120 or 240 Vac
- Max. maintenance temperature: 250°F (121°C)
- Max. continuous exposure temperature
Power-off : 450°F (232°C)
Minimum installation temperature: - 67°F (- 55°C)
Minimum installation temperature: - 67°F (- 55°C)
Available RTF FlexiPanel
Catalog number | Service voltage | Heat output watts | Current draw amps | Heat destiny w/in2 (w/m2) | Panel dimensions in (mm) |
---|---|---|---|---|---|
RTF - 1236 | 120 | 300 | 2.5 | 0.7 (1084) | 12 x 36 (305 x 1524) |
RTF - 1260 | 120 | 500 | 4.2 | 0.7 (1084) | 12 x 60 (305 x 1524) |
RTF - 1282 | 120 | 300 | 2.5 | 0.3 (465) | 12 x 84 (305 x 2134) |
RTF - 1284 | 120 | 500 | 4.2 | 0.5 (775) | 12 x 84 (305 x 2134) |
RTF - 2260 | 240 | 500 | 2.1 | 0.7 (1084) | 12 x 60 (305 x 1524) |
RTF - 2284 | 240 | 500 | 2.1 | 0.5 (775) | 12 x 84 (305 x 2134) |